Cable Size Calculator
Calculate appropriate cable size based on current, voltage drop, and cable length.
Single Phase: VD = 2 × I × R × L | Three Phase: VD = √3 × I × R × L
How to use:
Enter the load current (A), supply voltage (V), and cable length (m). The calculator will recommend the appropriate cable size based on current carrying capacity and voltage drop requirements.
Voltage Drop: The maximum allowable voltage drop is typically 3% for lighting circuits and 5% for power circuits. This ensures proper operation of connected equipment.
Standard Cable Sizes (Metric): 1.5, 2.5, 4, 6, 10, 16, 25, 35, 50, 70, 95, 120, 150, 185, 240, 300 mm²
Standard Cable Sizes (Imperial): 16, 14, 12, 10, 8, 6, 4, 3, 2, 1, 1/0, 2/0, 3/0, 4/0, 250, 300 AWG
Unit Conversion: You can switch between metric (mm², meters) and imperial (AWG, feet) units. The calculator will automatically convert values and display results in both systems.
Note: These calculations are based on standard conditions. Actual cable sizing should consider installation method, ambient temperature, grouping factors, and local electrical codes. Always consult with a qualified electrician for critical applications.
Published: December 2025 | Author: TriVolt Editorial Team | Last Updated: February 2026
Understanding Cable Sizing
Proper cable sizing is critical for electrical safety, efficiency, and code compliance. Undersized cables can overheat, cause voltage drops, and create fire hazards, while oversized cables waste materials and increase costs unnecessarily. Cable sizing involves balancing multiple factors including current carrying capacity, voltage drop limits, and installation conditions.
Electrical codes and standards specify maximum voltage drop percentages (typically 3% for lighting, 5% for power circuits) to ensure equipment operates correctly. Engineers must select cables that can safely carry the required current while maintaining acceptable voltage levels at the load.
Voltage Drop Calculations
Voltage drop occurs due to the resistance of the cable conductors. The formulas differ for single-phase and three-phase systems:
Single Phase:
VD = 2 × I × R × L
Three Phase:
VD = √3 × I × R × L
Where: VD = Voltage Drop (V), I = Current (A), R = Resistance per unit length (Ω/km), L = Length (km)
The factor of 2 in single-phase accounts for current flowing through both the outbound and return conductors (total conductor length is twice the one-way run length). The √3 factor in three-phase accounts for the phase relationship. Voltage drop percentage is calculated as: (VD / Supply Voltage) × 100%
Current Carrying Capacity
Each cable size has a maximum current rating based on:
- Conductor Material: Copper has higher conductivity than aluminum (approximately 1.6x better)
- Cable Size: Larger cross-sectional area allows more current
- Installation Method: Free air, conduit, buried - each affects heat dissipation
- Ambient Temperature: Higher temperatures reduce current capacity
- Grouping: Multiple cables together reduce individual capacity due to heat buildup
The calculator uses standard current ratings, but actual installations may require derating factors based on specific conditions.
Copper vs. Aluminum Conductors
Copper: Higher conductivity, better corrosion resistance, easier to work with, but more expensive. Standard choice for most applications.
Aluminum: Lower cost, lighter weight, but requires larger sizes for same current capacity (approximately 1.6x larger cross-section). Used in high-voltage transmission and large installations where cost savings justify the larger size.
When switching between materials, ensure the cable can handle the required current and meets voltage drop requirements.
Standard Cable Sizes
Cables are manufactured in standard sizes. Common metric sizes (mm²) include: 1.5, 2.5, 4, 6, 10, 16, 25, 35, 50, 70, 95, 120, 150, 185, 240, 300, and larger. Imperial sizes use AWG (American Wire Gauge) numbering, where smaller numbers indicate larger wires.
The calculator selects the smallest standard cable size that meets both current carrying capacity and voltage drop requirements.
Practical Applications
Residential Wiring
Proper cable sizing ensures outlets receive adequate voltage, prevents overheating, and complies with electrical codes. Common residential circuits use 2.5mm² or 4mm² cables for power outlets.
Industrial Installations
Large motors and equipment require careful cable sizing to handle high currents while maintaining voltage levels. Three-phase systems are common, requiring appropriate formulas.
Long-Distance Runs
Voltage drop becomes critical in long cable runs. Larger cables may be required not for current capacity, but to maintain acceptable voltage drop percentages.
Renewable Energy Systems
Solar and wind installations often have long cable runs from generation to load. Proper sizing maximizes efficiency and ensures system performance.
Real-World Examples
Example 1: Residential Circuit
A 20A circuit at 230V, 30 meters long, single-phase, 3% max voltage drop:
Max voltage drop = 230V × 0.03 = 6.9V
Required: 2.5mm² copper cable (handles 25A, meets voltage drop)
Actual voltage drop ≈ 4.2V (1.8%)
Example 2: Three-Phase Motor
A 15kW motor at 400V, 50 meters, 0.85 power factor, 5% max voltage drop:
Current = 15,000W / (√3 × 400V × 0.85) = 25.5A
Required: 6mm² copper cable (handles 40A, meets voltage drop)
Important Considerations
Installation Method
Cables in free air can carry more current than those in conduit or buried. Always apply appropriate derating factors based on installation method per local codes.
Ambient Temperature
High ambient temperatures reduce cable capacity. Derating factors must be applied in hot environments (e.g., attics, industrial settings).
Code Compliance
Always consult local electrical codes (NEC, IEC, etc.) for specific requirements. Codes may specify minimum sizes, derating factors, and installation methods.
Future Expansion
Consider future load increases when sizing cables. Oversizing slightly may be cost-effective if expansion is planned.
Tips for Using This Calculator
- Enter load current in amperes (not power - current is what determines cable size)
- Use line voltage (230V, 400V, 480V, etc.) for the supply voltage
- Select single-phase or three-phase based on your system
- Choose copper or aluminum based on your installation
- Typical voltage drop limits: 3% for lighting, 5% for power circuits
- Results show both metric (mm²) and imperial (AWG) sizes
- Always verify with local electrical codes and consult qualified electricians for critical applications
Common Pitfalls
Sizing for ampacity alone. NEC Table 310.16 gives the thermal limit — the current at which conductor insulation reaches its temperature rating. A 12 AWG copper at 75 °C is good for 25 A, but at 30 m of run length powering a 20 A continuous load, voltage drop will exceed 3% before you ever reach thermal limits. Cable size must satisfy both constraints, and the larger of the two usually wins on long runs.
Forgetting derating factors. NEC 310.15(C) requires current reduction when more than three current-carrying conductors share a raceway: 80% for 4–6, 70% for 7–9, 50% for 10–20. Add the ambient temperature correction from Table 310.15(B) and a cable rated 30 A in free air can drop to 17 A in a hot, crowded conduit. Most voltage-drop calculators, including this one, don't apply those factors automatically.
Aluminum sized like copper. Aluminum's resistance is ~1.6× copper, so conductors upsize one to two AWG steps for equivalent current. Aluminum also requires anti-oxidant paste at terminations and listed AL/CU-rated lugs (or purple-bodied CO/ALR devices on residential branch circuits). Mixing aluminum conductors with copper-only terminations causes the ~50% of residential aluminum fires reported through the 1960s–70s.
Using circuit length instead of one-way length in the single-phase formula. This calculator's VD = 2 × I × R × L already includes the factor of 2 for the round trip, so L is the one-way run from panel to load. Plugging in total loop length doubles the drop estimate and oversizes the cable. For three-phase balanced loads, L is still one-way because neutral current cancels.
Ignoring parallel-conductor ampacity rules. Parallel sets of 1/0 or larger may be installed per NEC 310.10(G), but every set must be identical in length, material, insulation, and raceway. Even small length imbalances cause disproportionate current sharing and can smoke the shortest conductor. For runs under 1/0, parallel is not permitted.
Frequently Asked Questions
What's the difference between THHN, XHHW, and USE-2?
All three are common copper building wire insulations. THHN is thermoplastic, rated 90 °C dry / 75 °C wet. XHHW is crosslinked polyethylene, 90 °C wet and dry. USE-2 is listed for direct burial and service-entrance use. For sizing, the 90 °C column in Table 310.16 only applies when all terminations are rated 90 °C — most equipment is rated 75 °C, forcing you to the 75 °C column regardless of insulation rating.
Why do NM-B (Romex) ratings look smaller than THHN of the same size?
NEC 334.80 restricts NM-B ampacity to the 60 °C column even though the insulation is rated 90 °C. This accounts for bundling in cavities and lack of ventilation. A 12-2 NM-B is 20 A; a 12 AWG THHN in conduit is 25 A at 75 °C.
How do I size for a VFD or inverter with high-frequency current?
VFD output cables see high dv/dt and reflected-wave effects that standard sizing ignores. Use VFD-rated cable (e.g., Belden 29500 series, or EMC-screened) and apply the VFD manufacturer's lead-length limits — often 15–30 m before output filters are required. For the input side, the Voltage Drop Calculator and Three-Phase Calculator still apply.
Does it matter if I use copper ground and aluminum phases?
Yes — mixing conductor materials across phase, neutral, and ground changes the fault-current path impedance and may require an upsized EGC per NEC 250.122(B). For long runs where phase conductors are upsized beyond the breaker's minimum, the grounding conductor must be upsized proportionally to keep ground-fault impedance low enough to trip the breaker.
Can I use the calculator for DC solar strings?
Yes, with adjustments. Use the single-phase formula (VD = 2 × I × R × L) because current returns through a second conductor, and pick a tighter voltage-drop target — 2% is common for PV array wiring to preserve MPPT headroom. NEC 690.8 also applies its own 125% continuous-duty multiplier on top of Isc. See the Voltage Drop Calculator for details.
Related Calculators
Complete the branch-circuit design with these related tools:
- Voltage Drop Calculator — verify drop for any specific cable choice.
- Wire Ampacity Calculator — cross-check NEC thermal limits for your gauge.
- Three-Phase Power — convert motor kW and PF into line current for sizing.
- Conduit Fill Calculator — confirm the picked conductors fit the raceway.
- Power Calculator — derive amps from connected load in watts.
- Fault Current Calculator — confirm AIC rating of downstream OCPDs with your cable impedance.
Disclaimer
This calculator is provided for educational and informational purposes only. While we strive for accuracy, users should verify all calculations independently, especially for critical applications. Actual cable sizing must consider installation method, ambient temperature, grouping factors, and local electrical codes. Always consult with a qualified electrician for critical applications. We are not responsible for any errors, omissions, or damages arising from the use of this calculator.
Also in Engineering
- → Voltage Drop — Calculate voltage drop across wires and components for troubleshooting
- → Ohm's Law Calculator — Calculate voltage, current, resistance, or power using Ohm's Law
- → Voltage Divider — Calculate output voltage in a voltage divider circuit
- → Power Calculator — Calculate electrical power from voltage and current