Wire Ampacity Calculator
Determine current-carrying capacity of conductors per NEC tables with derating factors.
NEC · US standard · AWG wire sizesAmpacity Results
NEC Ampacity Tables:
- Based on NEC Table 310.16 for conductors in raceway or cable
- Ambient temperature corrections per NEC 310.15(B)(1)
- Conduit fill derating per NEC 310.15(C)(1)
NEC 310.15 Ampacity Tables and Temperature Correction
CF = √[(Tmax − Tambient) / (Tmax − 30)]
Note: The calculator uses pre-tabulated correction factors from NEC Table 310.15(B)(2)(a) rather than this formula directly. The formula is shown for reference — results are equivalent for standard temperature ratings.
Common AWG ampacity at 75°C in conduit (copper):
14 AWG: 20 A | 12 AWG: 25 A | 10 AWG: 35 A | 8 AWG: 50 A | 6 AWG: 65 A
NEC Table 310.16 is the workhorse table for conductor ampacity — it covers copper and aluminium conductors from 14 AWG through 2000 kcmil, at insulation temperature ratings of 60°C, 75°C, and 90°C, for conductors in a raceway or cable (not free air). The table values assume an ambient temperature of 30°C (86°F) and no more than three current-carrying conductors in the raceway. When either condition changes, the tabulated values must be corrected before use. The temperature correction formula above shows that ampacity falls as ambient temperature rises because the conductor-to-ambient temperature differential — the thermal driving force for heat dissipation — shrinks. At an ambient of 50°C, a 75°C-rated conductor carries only 67% of its 30°C base ampacity.
The distinction between 60°C, 75°C, and 90°C ratings deserves careful attention. Most modern THHN and XHHW insulation is rated 90°C, which would suggest using the 90°C column for maximum ampacity. NEC 110.14(C) restricts this: when the conductor terminates at equipment rated only to 75°C (which includes most panelboards, circuit breakers, and lugs for conductors 100 A and below), the 75°C ampacity column must govern. The 90°C rating may still be used, however, as the starting point before applying correction factors — a useful benefit when heavy derating is required.
Conduit Fill Derating and Conductor Material Comparison
When four or more current-carrying conductors share a conduit, the mutual heating effect requires ampacity derating per NEC 310.15(C)(1). The adjustment factors are: 4-6 conductors, multiply by 0.80; 7-9 conductors, multiply by 0.70; 10-20 conductors, multiply by 0.50. Only current-carrying conductors count for this purpose — a neutral conductor carrying only unbalanced current in a balanced three-phase system is not counted, but a neutral carrying harmonic currents (common with non-linear loads like VFDs and computers) is counted because it carries significant current continuously. This distinction is one reason why electrical engineers specify oversized neutrals on circuits serving large quantities of single-phase electronic loads.
Aluminium conductors offer a significant weight and cost advantage over copper — roughly 30% of the weight and 50 to 60% of the cost per foot — but require two AWG sizes larger to carry the same current. A 12 AWG copper conductor rated at 25 A at 75°C requires a 10 AWG aluminium conductor to match it. Aluminium also requires anti-oxidant compound at all connections and listed aluminium-rated connectors, because aluminium oxide is a poor electrical conductor and forms quickly when exposed to air. For branch circuit wiring below 10 AWG, most jurisdictions and authorities having jurisdiction (AHJ) strongly discourage or prohibit aluminium due to the connection reliability issues that caused residential fires in the 1960s and 1970s when aluminium branch circuit wiring was common.
Voltage Drop Limits and AWG Selection in Practice
Ampacity establishes the thermal limit for conductor selection, but voltage drop establishes a separate constraint that is often more restrictive on long runs. NEC 210.19(A) informational note recommends limiting voltage drop on branch circuits to 3%, with a combined feeder and branch circuit drop of no more than 5% for the best efficiency of equipment. These are recommendations, not mandatory code requirements, but most engineers treat them as design criteria because excessive voltage drop causes motor overheating, lighting flicker, and equipment malfunction. The voltage drop for a single-phase run is Vdrop = 2 × I × R × L, where R is the resistance per foot from NEC Chapter 9 Table 8 and L is the one-way run length in feet. For three-phase circuits, replace the factor of 2 with √3.
As a practical guide, common AWG sizes and their NEC 310.16 ampacity at 75°C for copper conductors in conduit are: 14 AWG at 20 A (15 A for branch circuit breaker per 240.4(D)), 12 AWG at 25 A (20 A breaker), 10 AWG at 35 A (30 A breaker), 8 AWG at 50 A, 6 AWG at 65 A, 4 AWG at 85 A, 2 AWG at 115 A, and 1/0 AWG at 150 A. Note that NEC 240.4(D) caps overcurrent protection for 14 AWG at 15 A and 12 AWG at 20 A regardless of the conductor's tabulated ampacity, a safety measure for the most common residential and light commercial wiring sizes. For any run longer than about 75 feet at typical residential loads, re-running the voltage drop calculation with the next larger AWG is worthwhile — the small added material cost is often recovered quickly in lower energy losses and more stable voltage at the load end.
Worked Examples
Example 1: 40 A continuous load in a hot attic
A 40 A continuous load (say, a tankless water heater) runs through a 10 AWG copper THHN cable in a conduit passing through an attic that routinely reaches 40°C in summer. Four current-carrying conductors share the conduit.
Base ampacity, 10 AWG copper at 90°C = 40 A (NEC 310.16).
Temperature factor at 36–40°C for 90°C conductor = 0.82.
Conduit fill factor for 4 conductors = 0.80.
Adjusted ampacity = 40 × 0.82 × 0.80 = 26.2 A.
Because NEC 210.19 requires the conductor to be sized for 125% of a continuous load (40 × 1.25 = 50 A), 10 AWG is inadequate here — the next step is 8 AWG copper at 90°C (55 A base), which yields 55 × 0.82 × 0.80 = 36 A. Still short; 6 AWG at 75 × 0.82 × 0.80 = 49.2 A satisfies the 50 A target.
Example 2: Aluminium feeder for a 200 A panel
A 200 A residential service feeder uses aluminium conductor in a conduit buried under 30°C ambient soil, with three conductors (L1, L2, neutral). From Table 310.16 at 75°C, 4/0 AWG aluminium is rated 180 A — short of the 200 A target. Moving up to 250 kcmil aluminium gives 205 A, which meets the service rating at standard conditions with no derating. This is why NEC 310.16 shows 250 kcmil aluminium as the standard 200 A service size.
Example 3: Branch circuit for a 15 A receptacle
A standard 15 A general-purpose receptacle circuit uses 14 AWG copper. NEC 240.4(D)(3) fixes the maximum overcurrent protection for 14 AWG copper at 15 A regardless of its tabulated 20 A ampacity. Even though the calculator may report 20 A at 75°C, the breaker must be 15 A for residential branch circuits — this is the "small conductor rule" intended to protect the most common wiring sizes from overload.
Common Pitfalls
- Skipping the 125% rule for continuous loads. NEC 210.19(A) and 215.2(A) require conductors and overcurrent protection to be sized for 125% of any load that operates three hours or more continuously. A 40 A continuous load requires the circuit to be sized for 50 A, not 40 A.
- Reading the 90°C column when terminations are rated 75°C. NEC 110.14(C) ties the usable ampacity to the lowest-rated component in the circuit, which is usually the breaker lug. Use the 90°C column only for derating calculations, not for final ampacity when terminations are 75°C.
- Ignoring rooftop ambient-temperature adder. NEC 310.15(B)(3)(c) (earlier editions) or 310.15(E) requires an ambient-temperature adjustment for conduit within 7/8 inch of a rooftop — up to 33°C above the local ambient. An inspection failure here is common on rooftop HVAC feeders.
- Forgetting to count the neutral with non-linear loads. On circuits serving LED drivers, VFDs, or computer loads, the neutral carries harmonic current and counts as a current-carrying conductor for derating purposes (NEC 310.15(E)).
- Using aluminium where copper is required. Many panelboards are listed for copper only, and most jurisdictions require copper for 10 AWG and smaller branch circuits. Check listings and local amendments before specifying aluminium.
Frequently Asked Questions
Does this calculator replace the NEC?
No. It reproduces the NEC Table 310.16 values and applies the standard correction factors from 310.15, but the NEC contains dozens of other sections that can affect conductor sizing — voltage drop, grounding, parallel conductors, bundled cables, busway taps, and jurisdiction-specific amendments. Use the calculator for quick sizing checks, but rely on the current NEC edition and a licensed electrician for anything that will be permitted or inspected.
Why is there a separate 60°C column if most modern cable is rated 90°C?
The 60°C column applies when the circuit terminates at a component rated only to 60°C — older or unlisted equipment, some motor terminals, and certain legacy receptacles. NEC 110.14(C) requires the lowest of the three temperature ratings in the chain (conductor, termination, device) to set the allowable ampacity.
Is NEC Table 310.16 the only ampacity table?
No. Table 310.16 covers conductors in a raceway or cable (the most common case). Table 310.17 covers conductors in free air, which allow higher ampacity because heat dissipates faster. Tables 310.18 through 310.20 cover elevated-temperature rated conductors. For underground feeders, consult the 310.60 tables for direct-buried installations.
Do I need to derate for voltage drop too?
Voltage drop is a separate calculation — it does not derate the conductor's ampacity, but it may require you to upsize the conductor beyond what ampacity alone would allow. NEC 210.19(A) Informational Note recommends 3% on branch circuits and 5% overall. On long runs, voltage drop is usually the binding constraint, not ampacity.
What if my ambient temperature is cooler than 30°C?
You may apply a correction factor greater than 1.0, increasing the allowable ampacity. Refrigerated spaces and cold storage freezers can legitimately carry 10–15% more current on the same conductor. The calculator starts at 21–25°C (factor 1.0) because that covers most indoor installations — for colder ambient, consult NEC Table 310.15(B)(1) directly.
Related Calculators
- → Voltage Drop Calculator — pair with ampacity to size for long runs.
- → Cable Size Calculator — ampacity + voltage drop in one workflow.
- → Conduit Fill Calculator — confirm your conductors fit per NEC Chapter 9.
- → Transformer Sizing — upstream of every ampacity calculation.
- → Ohm's Law Calculator — the foundation for every electrical sizing problem.
Disclaimer
This calculator is provided for educational and informational purposes only. While we strive for accuracy, users should verify all calculations independently. We are not responsible for any errors, omissions, or damages arising from the use of this calculator.
Also in Engineering
- → 3-Phase Power — Calculate 3-phase power, current, voltage, and power factor
- → Airflow vs Static Pressure — Calculate airflow characteristics, velocity, and fan power for ducts and fans
- → Arc Flash Calculator — Calculate incident energy and arc flash boundaries for safety
- → ASHRAE Humidity Calculator — Calculate dew point and verify conditions against ASHRAE TC 9.9 environmental classes